Sikafloor® Conductive Set
Set with 10 earthing points
Set with 10 earthing points to connect electrostatic conductive Floor coverings to grounding.
- Good durability in terms of mechanical resistance
- Cost effective
- Easy to apply
- Stable connection
Usage
Sikafloor® Conductive Set is used to ground decorative and protective electrostatic conductive floor coverings used in automotive, electronics and pharmaceutical manufacturing, storage facilities and warehouses.Advantages
- Good durability in terms of mechanical resistance
- Cost effective
- Easy to apply
- Stable connection
Packaging
1 plastic box with all required single parts for 10 earthing points.
Product Details
Product Information
Shelf Life
Unlimited
Storage Conditions
The packaging must be stored properly in original, unopened and undamaged sealed packaging, in dry conditions at temperatures between +5°C and +30°C.
Application
Consumption
Consumption
Every earthing point is able to conduct approx. 200-300 m².
Ensure the longest distance of each earthing point in the area is max. 20 m to the next earthing point. For longer distances, additional earthing plates have to be placed.
Application steps
APPLICATION
- Prepare and prime the substrate in accordance with the relevant PDS of the uesed system.
- Drill a hole with diameter of 8 mm and a depth of > 50 mm.
- Remove all dust, loose and friable material and inserta size 8 dowel. The dowel must be flush with the floor surface.
- Screw the threaded rod with hexagon socket into the plug with an Allen key, so that 16 mm of the threaded rod protrude.
- Glue the copper strips (2 x 10 mm) on both sides of the hole.
- Place the large (D=60 mm) and middle (D=30 mm) washers over the threaded rod and secure with the nut (M6) so that the washers are pressed onto the copper strips with good contact.
- Push the transparent plastic hose over the threaded rod so that the hose fits tightly.
- Apply the conductive primer Sikafloor®-220 W Conductive
- Apply the conductive wearing course.
- After curing of Sikafloor® materials, remove the transparent plastic hose.
- Clean the head of the threaded rod properly. Fix the brass eyelet using the self‐locking nut (M 6) at the threaded rod.
- Connect the grounding cable with the brass eyelet.